Standard Technical Features of BTG System for Supercritical 660/800 MW Thermal Units
79
CHAPTER- 10
ELECTROSTATIC PRECIPITATOR
10.1 Design Data
The electrostatic precipitator(s) (ESP) of each unit shall be arranged in
minimum four (4) independently operating gas streams (casings) for 660 MW
unit and six (6) independently operating gas streams (casings) for 800 MW
unit. Each gas stream/ casing shall be provided in twin compartments. ESP
shall be designed to comply with the requirements stipulated under ‘guarantee
point’ and ‘design point’ in the table below:
Sl.
No.
Item Guarantee point Design point
i) Unit loading 100% TMCR 100% BMCR
ii) Type of coal Design coal Worst coal (maximum
ash coal from range)
iii) Ambient air condition 27
0
C temp. and 60%
RH
45
0
C temp. and 60%
RH
iv) Gas flow per steam
generator at the ESP
inlet when firing
respective coal (m
3
/sec)
To be worked out
when firing the
specified design coal
at TMCR.
To be worked out
when firing the
specified worst coal
with max. ash at
BMCR load,
considering 25%
excess air at
economiser outlet,
15% air heater in
leakage and 2% duct.
v) Gas temperature at ESP
inlet (
0
C)
125
0
C or as predicted
under conditions
stipulated above,
whichever is higher.
140
0
C or as predicted
under conditions
stipulated above,
whichever is higher.
vi) Inlet dust burden
(gm/Nm
3
)
To be worked out
based on 85% of ash
or actual predicted
whichever is higher
being carried forward
to ESP while firing
specified design coal.
To be worked out
based on 85% of ash
or actual predicted
whichever is higher
being carried forward
to ESP while firing
specified worst
(maximum ash) coal.
vii) No. of electrical fields
out of operation
One each in all the
passes
One each in all the
passes
viii) Outlet dust burden
(mm/Nm
3
)
50 mg/Nm
3
(maximum) or as per
MOEF’s requirement
whichever is more
80 mg/Nm
3
(maximum) or as per
MOEF’s requirement
whichever is more