Standard Technical Features of BTG System for Supercritical 660/800 MW Thermal Units
140
b) All analog signals for control purpose shall be acquired, validated,
processed and their respective data base updated at a maximum
interval of 250 milli-seconds except for some fast-acting control
loops for which the above-referred time shall be as per process
requirement. For signals required for information only, the above
functions shall be performed at an interval of within 1 second.
c) The 4-20 mA input analog cards shall be suitable for interfacing
transmitters giving 4-20mA analog signal along with superimposed
HART interface signals. 4-20 mA DC signal will only be used for
control purpose and superimposed HART signal will be used for
configuration, maintenance diagnostic and record keeping facility for
electronic transmitters and analysers etc. For non-HART 4- 20mA
analog inputs, conventional non-HART AI module shall be applied.
ii) Binary Signal Conditioning & Processing
a) The changeover type contacts (i.e. 'NC' + 'NO' together) shall be
wired to the control system for all the binary inputs required for
control purposes, except for inputs from MCC/switchgear, actuators
and inputs related to hardwired signal exchange among various
functional group for which non-changeover type contacts ('NC' or
'NO') shall be wired to the control system. The binary inputs
required for information purposes only shall be wired to control
system in the form of non-changeover type contacts.
b) The conditioning and processing functions to be performed as a
minimum for the binary inputs coming for control and information
purposes shall be:
1. 24V/ 48 V DC power supply for contact interrogation for all
potential free contacts with per point fuse protection or suitable
current limit feature/ isolation through opto-coupler.
2. Contact bounce filtering delay time of 15 milliseconds.
3. Facility for pegging the binary signal to logic one/zero or last
correct value in case of failure of binary input module.
4. Binary signal distribution to different users shall be in such a
way so as to ensure that a short/ground fault on one user is not
reflected to the other user.
5. Implementation of multiple measurement schemes for signals
for control purpose.
6. All binary signals shall be acquired, validated, processed, alarm
checked and their data base updated within one second. In
addition to this requirement, binary signals required for SOE
shall have a resolution of 1millisecond.