Standard Technical Features of BTG System for Supercritical 660/800 MW Thermal Units
112
14.5.6 The temperature in the flash tanks shall be maintained by using condensate
spray or service water spray (for flash tanks open to atmosphere). The spray
shall be automatically controlled. However, for flash tanks open to
atmosphere continuous spray through an orifice shall also be acceptable.
14.5.7 Facility shall be provided for remote manual operation of the drain valves
from the control room. Motor operated drain valves shall be interlocked to
open/ close as per the process requirements. Position indication of drain
valves shall be provided in the control room.