2
I. PRODUCT DESCRIPTION
The Crown Mega-Stor series indirect water heater is designed to generate domestic hot water in conjunction with a hot water
boiler using forced boiler water circulation. This indirect water heater consists of a stainless steel tank in which a smooth stainless
steel coil is located. Boiler water is pumped through the coil and heats the water in the tank. This tank is not intended for use in
systems.
IMPORTANT NOTE
Some localities require indirect water heaters having a relief valve capacity in excess of 200,000 BTU/hr to be con-
structed and stamped in accordance with ASME requirements. Check with the local authority having jurisdiction before
installing an MS-79 or MS-119 with a boiler or boilers having a total gross output in excess of 200,000 BTU/hr.
II. SPECIFICATIONS
TABLE 2.1: AHRI PERFORMANCE SPECIFICATIONS
Notes:
AHRI ratings based on 77F DHW temperature rise (135F outlet temp) and 180F boiler supply temperature. The ratings in
be obtained under different conditions.
Pressure Ratings:
Maximum Allowable Tank Working Pressure - 150 psi
Design Hydrostatically Tested to 300 psi
Model
First Hour
Rating
Continuous
Draw Rating
Standby
Loss
(°F/hr)
Minimum
Boiler
Output
(MBH)
Boiler Water Through Coil
(Gal/hr) (Gal/hr)
Min Flow
(Gal/min)
Head Loss
(ft w.c.)
MS-26 144 121 1.7 77 8.0 2.5
MS-40 195 157 1.4 102 8.0 3.0
MS-53 226 179 0.9 114 8.0 3.5
MS-79 287 218 1.0 145 8.0 4.8
MS-119 472 384 1.4 225 12.7 7.9
MSH-40 151 116 1.4 75 8.0 2.5
MSH-53 203 158 1.3 101 8.0 3.5