TWZ/CT/ODV Series
Oil-Fired Hot Water Boilers (Less Tankless Heater)
INSTALLATION SUPPLEMENT FOR BOILERS
EQUIPPED WITH HONEYWELL L7248L
“2012 COMPLIANT” BOILER CONTROL
These instructions must be afxed on or adjacent to the boiler
WARNING: Improper installation,
adjustment, alteration, service or
maintenance can cause property
damage, injury, or loss of life.
For assistance or additional
information, consult a qualied
installer, service agency or the oil
supplier. Read these instructions
carefully before installing.
D ESIGNED TO L EAD
Manufacturer of Hydronic Heating Products
P.O. Box 14818 3633 I. Street
Philadelphia, PA 19134
www.crownboiler.com
Page view 0
1 2 3 4 5 6 ... 15 16

Summary of Contents

Page 1 - TWZ/CT/ODV Series

TWZ/CT/ODV Series Oil-Fired Hot Water Boilers (Less Tankless Heater)INSTALLATION SUPPLEMENT FOR BOILERS EQUIPPED WITH HONEYWELL L7248L“2012 COMPLIANT”

Page 2

81sec.1sec. 1sec. FIGURE 12.3: TYPICAL OPERATING MODE DISPLAY (BOILER TEMP SHOWN)TABLE 12.2: STATUS CODESStatus # Description Meaning1S

Page 3

9TABLE 12.5: ADJUSTMENT MODE PARAMETERSStatus # DescriptionFactory Setting Permissible Range HLHigh Limit Set point 180F 140-220FHdFHigh Limit Differe

Page 4

10HdF (High limit differential) - If the boiler shuts off on high limit, the water temperature must fall by an amount equal to the differential during

Page 5

11TABLE 12.7 SUMMARY OF CIRCULATOR BEHAVIOR Thermostat Inputs Use of “ZC” ZoneParameters Circulator OutputsT-T “DHW”2nd Zone (Zc)DHW Priority (Pt) “C

Page 6 - Riello 530SE:

12XIV Trouble Shooting The following tables contain trouble shooting tables for use in diagnosing control problems. When using these tables the fol

Page 7

13TABLE 14.1 - FAULTS WITHOUT ERROR CODE PRESENTDisplayed Codes Problem Possible CauseStA 1hr OFFdh OFFBurner and Circulator OffThermostat/s not calli

Page 8 - XII Operation

PN: 980200 08/12Manufacturer of Hydronic Heating ProductsP.O. Box 14818 3633 I. StreetPhiladelphia, PA 19134www.crownboiler.com

Page 10

1I Basic InformationA. What is this Supplement For? This instruction manual supplement provides important information on the installation and oper

Page 11

2120 Volt Wiring1) - The boiler should be provided with its own 15A branch circuit with fused disconnect. 120VAC power con-nections are made inside

Page 12

3 FIGURE 10.0: TWZ, CT BOILERS: CONNECTIONS DIAGRAM FOR L7248L AQUASTAT®

Page 13

4 FIGURE 10.1: TWZ, CT BOILERS: CONNECTIONS DIAGRAM FOR BURNER PRIMARY CONTROLS Carlin 40200: Beckett 7505: Riello 530SE:

Page 14 - XIV Trouble Shooting

5 FIGURE 10.2: ODV BOILERS: CONNECTIONS DIAGRAM FOR L7248L AQUASTAT®

Page 15

6XII OperationA. General Information This boiler uses a proprietary version of the Honeywell L7248L Aquastat® to regulate water temperature and to m

Page 16 - PN: 980200

7STATUSMODE:6W$=CurrentStatus(Table12.2)PressandHoldI,↑,and↓foratleast3sectoenterADJUSTMENTMODEPressItoenterOPERATINGMODEEW=