Crown Boiler TWZ125 Specifications Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 32
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
17
FIGURE 14: TANKLESS HEATER PIPING
IX Fuel Line Piping
Fuel line piping design, materials and construction must be in accordance with local building codes, requirements of the local
authority having jurisdiction, and, the latest edition of Installation of Oil-Burning Equipment (ANSI/NFPA 31). Refer also to
the instruction manuals provided with the burner and oil pump.
Depending on the location of the fuel oil storage tank in relation to an oil burner, there are four types of oil piping systems
generally being used:
a) ONE-PIPE GRAVITY SYSTEM - used when a fuel oil storage tank is positioned above an oil burner fuel pump. See
Figure 15. A vertical distance from top of the tank to center line of the pump (Dimension ‘H’) over 8 feet will result in
a pump inlet pressure in excess of the 3-psi limit in NFPA-31.
FIGURE 15: ONE-PIPE GRAVITY SYSTEM