Crown Boiler 32-475ECS Installation Manual

Browse online or download Installation Manual for Water heaters & boilers Crown Boiler 32-475ECS. Crown Boiler 32-475ECS Installation manual User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 16
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
D e s i g n e D t o L e a D
Tel: (215) 535-8900 • Fax: (215) 535-9736 • www.crownboiler.com
Manufacturer of Hydronic Heating Products
P.O. Box 14818 3633 I. Street
Philadelphia, PA 19134
Series 32ECS
Gas-Fired Natural Draft Steam or Water Boilers
INSTALLATION SUPPLEMENT FOR:
32-380ECS
32-475ECS
EQUIPPED WITH 24 VOLT CONTROL SYSTEMS
WARNING: Improper installation,
adjustment, alteration, service or
maintenance can cause property
damage, injury, or loss of life. For
assistance or additional information,
consult a qualied installer, service
agency or the gas supplier. Read
these instructions carefully before
installing.
Page view 0
1 2 3 4 5 6 ... 15 16

Summary of Contents

Page 1 - Series 32ECS

D e s i g n e D t o L e a DTel: (215) 535-8900 • Fax: (215) 535-9736 • www.crownboiler.comManufacturer of

Page 2

Figure F: Water Boiler Control Installation (Less Tankless Heater Version Shown)Figure E: Blocked Vent Switch Installation8

Page 3

6) Once the ignition module detects the presence of a pilot ame, voltage is applied across the main valve (terminals “MV” and “MV/PV”), opening the

Page 4 - IX Water Boiler Piping

380 475 380 475IAPART # (STANDARD) 310000 310001 310002 3110053 3110063 310405 310406 311026 311020 311010 310400 311027 311028 311031 1 EA. 1 EA.BOI

Page 5 - XI Control System Wiring

BASE SIDE CARTON - See Installation ManualJACKET SIDE PANEL CARTON- See Installation ManualWATER AND STEAM BOILER CARTONS - As shown in Installation M

Page 6 - Figure A: Steam Boiler Wiring

12STEAM PROBE CONTROL SUB ASSY 3513210 1LWCO, CG400 WITH "P" PROBE 400824 1BLOCKED VENT SWITCH ASSY 960128 1GLASS SET (20-104-10, 8" C

Page 8 - HONEYWELL

PN 980895 05/10 Tel: (215) 535-8900 • Fax: (215) 535-9736 • www.crownboiler.comManufacturer of Hydronic Heat

Page 10

I Product Description This supplement covers information not included in the standard Series 32 installation manual that is unique to the

Page 11

VII VentingRefer to installation manual. Vent sizing for the 32-380ECS should always be done in accordance with the National Fuel Gas Code. A vent

Page 12 - SECTION JOINER CARTON

WARNINGAll wiring and grounding must be done in accordance with the authority having jurisdiction or, in the absence of such CAUTIONMake sure that dam

Page 13

“BURNER”“BURNER”THTR+ROBERTSHAW7000DERHCGAS VALVEVENT DAMPER (NOTE 2)NOTE 2LESS VENTDAMPER2. ON BOILERS LESS VENT DAMPER, DAMPER HARNESS NOT USED. RED

Page 14 - ECS STEAM TRIM CARTON

Sequence of Operation - Steam Boiler1) When the boiler is energized, 24 volts is immediately applied to terminals “1” (blue) and “4” (yellow) on the v

Page 15

2HIGH LIMITLOWLIMITHONEYWELLL8124ETHTR+ROBERTSHAW7000DERHCGAS VALVEPILOT VALVEMAIN VALVERDRDRD/YERDRD/YEALARMALARMFigure C: Water Boiler Wiring (With

Page 16 - PN 980895

equipped with a reset button which must be pressed to restore normal burner operation. An open blocked vent switch is indicative of a problem with the