CWI Series
Gas-Fired Natural Draft Water Boilers
INSTALLATION INSTRUCTIONS
These instructions must be affixed on or adjacent to the boiler
WARNING: Improper installation,
adjustment, alteration, service or
maintenance can cause property
damage, injury, or loss of life. For
assistance or additional informa-
tion, consult a qualified installer,
service agency or the gas
supplier. Read these instructions
carefully before installing.
Models:
CWI069
CWI103
CWI138
CWI172
CWI207
CWI241
CWI276
CWI310
CWI345
CWI379
Page view 0
1 2 3 4 5 6 ... 55 56

Summary of Contents

Page 1 - CWI Series

1D E S I G N E D T O L E A DTel: (215) 535-8900 • Fax: (215) 535-9736 • www.crownboiler.comManufacturer of Hydronic Heating Pro

Page 2 - I Product Description

109sealed tight.13) Do not install the vent damper in any portion of the vent system which is used by appliances other than the boiler beinginstalled.

Page 3 - II Specifications

1110 FIGURE 8: CWI BOILER TYPICAL VENT SYSTEM INSTALLATION AND COMPONENTS FIGURE 9: VENT DAMPER INSTALLATION DETAILS

Page 4 - IV Locating the Boiler

1211*VII Gas PipingGas piping to the boiler must be sized to deliver adequate gas for the boiler to fire at the nameplate input at a line pressurebet

Page 5 - “X” (RH CLEARANCE)

1312VIII System PipingStandard PipingFigure 11 shows typical boiler system connections on a single zone system. Additional information on hydronic sy

Page 6

146) Low Water Cut-Off (Required in some situations) - A low water cutoff is required when the boiler is installed aboveradiation. In addition, some

Page 7

1514 FIGURE 12: INDIRECT WATER HEATER BOILER SIDE PIPING FIGURE 11: STANDARD BOILER PIPING

Page 8

165) Piping with a Chiller - If the boiler is used in conjunction with a chiller, pipe the boiler and chiller in parallel as shown inFigure 15. Use i

Page 9 - VI Venting

17 FIGURE 15: BOILER PIPING WITH CHILLER FIGURE 14: ISOLATION OF BOILER FROM SYSTEM WITH A HEAT EXCHANGER16

Page 10

1817IX TANKLESS HEATER PIPINGIf the CWI is installed with an optional tankless heater, pipe the heater as shown in Figure 17. The components in thissy

Page 11

19183) Pressure Relief Valve (Required) - Limits the pressure in the tankless heater and piping. Use an ASME constructed valvedesigned for domestic wa

Page 12 - VII Gas Piping

2Table of ContentsI. Product Description ... 1II. Specifications ...

Page 13 - VIII System Piping

20IX WiringSingle Zone Wiring1) 120 Volt Wiring - The boiler should be provided with its own 15A branch circuit with fused disconnect. All 120 vol

Page 14 - Piping for Special Situations

2120 FIGURE 19: WIRING DIAGRAM, INTERMITTENT IGNITION (EI) SYSTEM LESS TANKLESS HEATER FIGURE 20: WIRING DIAGRAM, STANDING PILOT WITH TANKLESS H

Page 15 - BOILER SIDE PIPING

2221 FIGURE 21: WIRING DIAGRAM, INTERMITTENT IGNITION (EI) SYSTEM WITH TANKLESS HEATERWiring Variations1) Multiple Circulator Zones – Figure 22 sh

Page 16

2322FIGURE 23: ZONE WIRING USING HONEYWELL V8043F ZONE VALVES(FACTORY WIRING NOT SHOWN - SEE FIGURES 18 - 21)FIGURE 22: CIRCULATOR ZONE WIRING USING

Page 17

2423CWI Control System – Sequence of Operation(Refer to Figures 18 - 21 for ladder and connection diagrams)Sequence of Operation, Standing Pilot, Less

Page 18 - IX TANKLESS HEATER PIPING

2524Sequence of Operation, Intermittent Ignition, Less Tankless Heater1) When the boiler is energized, 24 volts is immediately applied to terminals

Page 19

26XI Start-up and CheckoutUse the following procedure for initial start-up of the boiler:1) Make sure that the boiler and system are filled with wate

Page 20 - V8295A

27WARNING• NEVER USE A FLAME TO CHECK FOR GAS LEAKS.• MAKE SURE THAT THE AREA AROUND THE BOILER IS CLEAR AND FREE FROM COMBUSTIBL

Page 21 - (NOTE 2)

282715) Check the manifold pressure and adjust if necessary. To do this, use the following procedure:a) Connect a manometer to the inlet pressure tap

Page 22 - Wiring Variations

292816) Test thermostat operation while the boiler is running. Turn the thermostat to the lowest setting. For standing pilot boilermodels, pilot burne

Page 23

3TABLE 1: CWI SPECIFICATIONS2II SpecificationsFIGURE 1: CWI BOILERS - GENERAL CONFIGURATIONINPUT(MBH) (MBH)(Gal/min)"A" "B" "

Page 24

30A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly.B. BEFORE LIGHT

Page 25

3130A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly.B. BEFORE LIG

Page 26 - XI Start-up and Checkout

3231A. This appliance is equipped with an ignition device which automatically lights the pilot. Do try to light the pilot by hand.B. BEF

Page 27

3332A. This appliance is equipped with an ignition device which automatically lights the pilot. Do try to light the pilot by hand.B. BEF

Page 28

34 FIGURE 28a: GAS VALVE DETAIL - HONEYWELL VR8204 AND VR8304 (INTERMITTENT IGNITION) FIGURE 27a: GAS VALVE DETAIL - HONEYWELL VR8200 OR VR830

Page 29

3534XI Service and MaintenanceThe following routine maintenance should be performed on an annual basis:1) Turn off electrical power and gas supply to

Page 30 - TO TURN OFF GAS TO APPLIANCE

36Heat Exchanger Cleaning Procedure1) Turn off electrical power and gas supply to the boiler.2) Disconnect the damper and vent connector from the boil

Page 31

3736XIII TroubleshootingThe following pages contain troubleshooting charts for use in diagnosing control problems. To use these charts, go tothe box

Page 32 - OPERATING INSTRUCTIONS

38Troubleshooting Chart for CWI Boilers Without Tankless HeatersCaution: Read page 36 before attempting to use this chart37Boiler Equipped With Dampe

Page 33

3938Main burners light?24 volts across B1 &B2 ?Ref er to standing pilot or intermittent ignition troubleshooting chart (page 41 or 42).*Def ective

Page 34

43III Before Installing1) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict accordance

Page 35 - XI Service and Maintenance

4039Troubleshooting Chart for CWI Boilers Equipped with Tankless Heaters and DampersCaution: Read page 36 before attempting to use this chartNo call f

Page 36

4140120 volts across terminals at circulator?Do bur ner sshut dow n before gage temp exceeds high limit setting +15F?Circulator start?120 volts at C1&

Page 37 - XIII Troubleshooting

42Standing Pilot Ignition System Troubleshooting ChartPilot lit?Main burners light?YTurn control on gas valve to PILOT. Depress red button and light

Page 38

4342Does spark stop when pilot lights?24 volts across terminals 2&3 at S8600?Spark across ignitor/sensor gap?YCan you hear sparking?*Faulty S8600

Page 39

4443XIV PARTS The following parts may be obtained from any Crown distributor. To find the closest Crown distributor, consult the area Crownrepresent

Page 41

464569 103 138 172 207 241 276310 345 37942 1" BURNER LESS PILOT BRACKET 150501 2 ea. 4 ea. 6 ea. 8 ea. 11 ea. 13 ea. 15 ea. 17 ea. 20 ea. 22 ea.

Page 43

484769 103 138 172 207 241 276310 345 37975 LEFT SIDE JACKET PANEL 1 ea. 850301 850301 850301 850301 8503012 8503012 8503012 8503015 8503015 850301576

Page 45

54• If the right side 24” service clearance is reduced, adequate clearance must be maintained to easily read and access thecontrols. Alternatively, ac

Page 46

50A. Before Installing1) Thoroughly inspect the cast iron heat exchanger for any shipping damage, i.e. cracks in the castings, broken lugs orpunctures

Page 47

5150FIGURE A1: BASE, HEAT EXCHANGER, FLUE COLLECTOR ASSEMBLY

Page 48

52side panel installed in the previous step and secure with three #10 sheet metal screws.5) Install the left side panel in the same manner as the righ

Page 49

5352FIGURE A2: JACKET INSTALLATION

Page 50

54F. Electrical Wiring Connections(Also refer to wiring diagrams in Part X of the installation manual)1) A pre-wired limit control (L8148E or L8124E)

Page 51

5554FIGURE A3: TAPPING LOCATIONS (SEE TEXT FOR TAPPING USES)

Page 52 - D. Gas Valve Installation

56Tel: (215) 535-8900 • Fax: (215) 535-9736 • www.crownboiler.comManufacturer of Hydronic Heating ProductsP.O. Box 14818 3633 I. StreetPhiladelph

Page 53

6• Caulking and sealants are applied to areas such as joints around window and door frames, between sole plates andfloors, between wall-ceiling joints

Page 54 - G. Complete Installation

76 FIGURE 4: ALL AIR FROM OUTDOORS, VENTILATED CRAWL SPACE AND ATTIC FIGURE 5: ALL AIR FROM OUTDOORS, VIA VENTILAT

Page 55

8 FIGURE 6: ALL AIR FROM OUTDOORS, USING OPENINGS INTO BOILER ROOM FIGURE 7: ALL AIR FROM OUTDOORS, USING HORIZONTAL D

Page 56 - Philadelphia, PA 19134

98• The “free area” of an opening takes into account the blocking effect of mesh, grills, and louvers. Where screens are used,they must be no finer t