Crown-boiler MWC116ENL User Manual

Browse online or download User Manual for Water boiler Crown-boiler MWC116ENL. Crown Boiler MWC116ENL User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 88
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Models:
MWC116ENT
MWC116ELT
MWC116ENL
MWC116ELL




 
: Improper installation, adjustment, alteration,
service or maintenance can cause property damage, injury,
or loss of life. For assistance or additional information, con-
sult a qualied installer, service agency or the gas supplier.
This boiler requires a special venting system. Read these
instructions carefully before installing.
D E S I G N E D T O L E A D
Manufacturer of Hydronic Heating Products
P.O. Box 14818 3633 I. Street
Philadelphia, PA 19134
Tel: (215) 535-8900 • Fax: (215) 535-9736 • www.crownboiler.com
D
E S I G N E D T O
L
E A D
Page view 0
1 2 3 4 5 6 ... 87 88

Summary of Contents

Page 1 -  

Models:MWC116ENTMWC116ELTMWC116ENLMWC116ELL    

Page 2

8Figure 5.1 Wall Mounting Hole Locations

Page 3 - Table of Contents

9Figure 5.2 Boiler Mounting

Page 4 - I Product Description

10VI Air for VentilationWARNINGOutdoor combustion air must be piped to the air intake. Never pipe combustion air from areas containing contaminates su

Page 5

11Figure 6.1: Boiler Installed In A Confi ned Space, Ventilation Air From InsideStep 2a (contd.)If the total volume of both the boiler room and the roo

Page 6 - II Specifi cations

12VII VentingWARNINGFailure to vent this boiler in accordance with these instructions could cause fl ue gas to enter the building resulting in severe p

Page 7 - IV Locating the Boiler

132 (contd.)Example: A 60/100mm concentric vent system is planned for a horizontally vented MWC116 which has the following components: 60/100mm Elbow

Page 8 - Combustibles = 1”

14Table 7.1: Summary Of Horizontal Venting Options VENT OPTION # 1 2 3 4CLASSIFICATION USED IN THIS MANUALHORIZONTAL CONCENTRIC HORIZONTAL CONCENTRICH

Page 9 - V Mounting The Boiler

15Table 7.3a: Crown Concentric 60/100 Vent Components (Vent Options 1,2)CROWN PN DESCRIPTION SIZEUSED ON VENT OPTION #COMMENTS340509 60/100mm ELBOW A

Page 10

16Figure 7.4a: Location Of Vent Terminal Relative To Windows, Doors, GradeFigure 7.4b: Location Of Vent Terminal Relative To Meters And Forced Air Inl

Page 11 - Figure 5.2 Boiler Mounting

17Permitted Terminals for Vertical Venting6) - Use Crown PN 230532 with the appropriate ashing (Table 7.3b) Vertical Vent Terminal Locations (Vent

Page 13

18Figure 7.7: Vertical Concentric Vent System (Vent Option 5)

Page 14 - VII Venting

19B. Removing an Existing Boiler From a Common Chimney Read this only if the MWC boiler is replacing an existing boiler that is being removed from

Page 15

20C. Assembly of Crown 60/100mm Concentric Venting(IMPORTANT - Skip to Section D for 80/125mm Concentric Vent Assembly)WARNINGFailure to follow the in

Page 16

21FIGURE 7.20: INSTALLATION OF 60/100 ADAPTORS ON BOILERFIGURE 7.21: DIMENSION “L”

Page 17

22If additional pieces of pipe are used, install them starting at the boiler elbow. Support each section of straight pipe 4) at its female end. Use lo

Page 18

23Figure 7.25: Attaching 60/100mm Terminal SectionFigure 7.24: Preparing 60/100mm Terminal Section For Installation In The Wall

Page 19

24D. Assembly of Crown 80/125mm Concentric Venting(IMPORTANT - See Section C for 60/100mm Concentric Vent Assembly)WARNINGFailure to follow the instru

Page 20

25Figure 7.31a: Cuttable Straight SectionFigure 7.31b: Non Cuttable Straight SectionInstallation of the MWC116 with 80/125mm venting requires the use

Page 21

263) (contd.) To cut the straight sections listed above refer to Figure 7.32 and the following instructions:Determine the required length of the a) o

Page 22

27Figure 7.33b: Joining Non-Cuttable PipeFigure 7.33a: Joining Cuttable Pipe

Page 23 - FIGURE 7.21: DIMENSION “L”

1Table of Contents I. Product Description 2 II. Specifi cations 4 III. Before Installing 5 IV. Locating The Boiler 5 V. Moun

Page 24

28Figure 7.34a: Dimension “L”, 80/125mm Horizontal TerminalFigure 7.34b: Cutting Outer Pipe Of 80/125mm Horizontal Terminal80/125mm Horizontal Termina

Page 25

29Figure 7.34c: Cutting Inner Pipe Of 80/125mm Horizontal TerminalFigure 7.34d: Completing 80/125mm Horizontal Terminal Installation

Page 26

30 Vertical Terminal Installation6) - In addition to the vertical terminal, either a Flat Roof Flashing (PN 230533) or Sloped Roof Flashing (PN 2305

Page 27

31Figure 7.35b: Cutting Vertical TerminalFigure 7.35c: Completing Vertical Terminal Installation

Page 28

32Figure 7.36: Chimney Chase InstallationWARNINGDo not attempt to construct a vertical vent system inside a chimney that is used to vent a • fi replace

Page 29

33E. Condensate Trap and Drain Line All condensate which forms in the boiler or vent system leaves the boiler through the condensate trap. This trap

Page 30

34VIII Gas PipingGas piping to the boiler must be sized to deliver adequate gas for the boiler to fi re at the nameplate input at an inlet pressure bet

Page 31

35Figure 8.2: Gas Connection To Boiler

Page 32 - Figure 7.35a: Dimension “H”

36IX System PipingCAUTIONInstall boiler so that the gas ignition system components are protected from water (dripping, • spraying, rain, etc) during a

Page 33

37Expansion Tank (Included & Required)4) – This boiler is equipped with a built in expansion tank. This tank is suitable for use on systems havi

Page 34

2I Product DescriptionThe MWC Series are gas fi red condensing boilers designed for use in forced hot water heating systems requiring supply water temp

Page 35

38B. Boiler Connections Boiler supply and return connections are located on the bottom of the boiler as shown in Figure 9.4. Copper 3/4” tail pieces

Page 36 - VIII Gas Piping

39Figure 9.4: Supply And Return Tailpiece InstallationC. Piping for Special Situations Certain types of heating systems have additional requirements.

Page 37

40Figure 9.6: Chiller PipingFigure 9.5: Primary-Secondary Piping

Page 38 - IX System Piping

41Figure 9.7: MWC116E*T (Combi) Internal Boiler-Side Piping Schematic

Page 39 - Figure 9.1: Basic Piping

42Figure 9.8: MWC116E*L (Heat-Only) Internal Piping Schematic

Page 40 - B. Boiler Connections

43WARNINGLike all domestic water heaters, the MWC is capable of generating water that is hot enough to cause injury or death due to scalding. To minim

Page 41 - D. Internal Boiler Piping

44Figure 10.1: DHW PipingFigure 10.2: DHW Tailpiece Installation

Page 42 - Figure 9.6: Chiller Piping

45Figure 10.3: MWC116E*T (Combi) Internal DHW-Side Piping Schematic

Page 43

46XI WiringWARNINGAll wiring and grounding must be done in accordance with the authority having jurisdiction or, in the absence of such requirements,

Page 44

47Figure 11.1: Accessing Electrical ConnectionsFigure 11.2: “Whip”Boiler EndField Supplied J-Box End

Page 45 - X. Domestic Water Piping

3Figure 1.1: MWC Boiler Principle Components

Page 46 - Figure 10.1: DHW Piping

48Figure 11.3: Location of Terminal Blocks and 7/8 Hole for WhipFigure 11.4: Electrical Connections Inside Control Box.

Page 47

49Figure 11.5: Field Wiring - 120VAC Thermostat Figure 11.6: Field Wiring - 24V Thermostat Using Installer-Supplied Fan Center

Page 48 - XI Wiring

50ye bk wh gy bu rdbkgygygyMtCOMNOCOMNONCbkbubnrdgnyegywhburdbkbuwhgybugnyebk bkubeyngygbkbkbubububurdbkygygL Nrd bu bn gnye gnyegnye bubnburdgnyewhgy

Page 49 - J-Box End

51XII Start-up and CheckoutUse the following procedure for initial start-up of the boiler:If not already done, fl ush the system to remove sediment and

Page 50

52Check all new water and gas piping for leaks and purge piping sections that are fi lled with air. Fix any 3)leaks found immediately. See the National

Page 51

53 The burner may not light on the fi rst try. The most likely cause of this problem on a new installation • is a gas line that has not been completely

Page 52

54WARNINGThe gas valve manifold pressures are factory set and should rarely need to be adjusted. Failure to adjust the gas valve in strict accordance

Page 53 - Vent Cap

55 Manifold Pressure TapInlet Pressure TapModulation LeadsFigure 12.6: Gas Pressure Taps Low Fire Adjustment(Inner Hex Shaft)High Fire Adju

Page 54 - Shaft Screw Cover

56MWC Series Lighting and Operating InstructionsWARNING: If you do not follow these instructions exactly, a fire or explosion may resultcausing proper

Page 55

57Remove the monometer and make sure that the inlet and manifold pressure tap screws are closed9) Check the entire gas train for leaks. Fix any leaks

Page 56

4Table 2.2: RatingsMODEL* APPLICATIONMAX.INPUT (BTU/hr)MINIMUM INPUT (BTU/hr)D.O.E. HEATING CAPY. (BTU/hr)IBR NET RATING (BTU/hr)AFUE (%)DHW Output (G

Page 57 - (Outer Brass Nut)

58XIII OperationLamp 2Lamp 1Lamp 3Heating System KnobDHW Thermostat (Combi Only)Flame Lockout LampFlame Reset ButtonFigure 13.1: Control Pan

Page 58 - TO TURN OFF GAS TO APPLIANCE

59WARNINGThe domestic water thermostat on the Maui is not intended to serve as a scald protection device. Under certain conditions, it is possible for

Page 59

60 Sequence of Operation(Also Refer to Figures 9.7, 9.8, 10.3, 11.7)Upon a call for heat from the room thermostat, the circulator is started.1) If t

Page 60 - XIII Operation

61Lamp Number 1 2 3 Meaning (Short pulse every 4 seconds): Heating System Knob in “Off” position. Boiler will not respond to call for heat or DHW. Fr

Page 61 - 131F Target DHW Temp

62XIV. Service and MaintenanceIMPORTANTWarranty does not cover boiler damage or malfunction if the following steps are not performed at the intervals

Page 62 - Sequence of Operation

63WARNINGSoot deposits in the fl ue passages are a sign that the boiler may be operating at high carbon monoxide (CO) levels. After cleaning the boiler

Page 63 - (See Part XV for Error Codes)

64Figure 14.2: InducerNeg. Pressure Ta pVenturiWARNINGDo not leave the boiler in service with the Inner Cover removed.• Do not attempt to fi re this

Page 64 - XIV. Service and Maintenance

65Figure 14.3: Condensate Trap Removal Condensate TrapSpring ClipFigure 14.4: Location of Pressure Switch Taps and Limit Reset Buttons

Page 65

66XV. TroubleshootingWARNINGTurn off power to boiler before replacing fuses or working on wiring.Figure 15.2: Fuse LocationLine Voltage ConnectionsF

Page 66 - Neg. Pressure Ta p

67Table 15.3: Error CodesLamp Number 1 2 3 Flame L.O. Lamp Meaning Corrective Action Differential Water Pressure Switch Failed to Close Afte

Page 67 - Spring Clip

5III Before InstallingSafe, reliable operation of this boiler depends upon installation by a professional heating contractor in 1)strict accordance wi

Page 68 - Line Voltage Connections

68Push reset button on Flue Temp Limit (Fig 14.4)Reset Boiler Does Boiler Start?Reset Boiler Push reset button on Supply Temp Limit (Fig 14.4)Does Boi

Page 69 - Table 15.3: Error Codes

69XVI PartsThe following parts may be obtained from any Crown distributor. To fi nd the closest Crown distributor, consult the area Crown representativ

Page 70

70C.h. flow group and three way diverter valve (Model combi)212223 (upper part)2025*28 29 30 31 323334242420107726272036181789423 (lower part)35* Incl

Page 71 - XVI Parts

71C.h. flow and return groups (Model c.h. only)2145789203633343528 29 30 31 328910147*7146617* Includes items 20, 28, 29, 30, 31, 32, 3626273

Page 72

72Pump and main circuit assembly (Model combi)454741574853 5255545062637615856494141603739394042404344594638338445158765764

Page 73

73Pump and main circuit assembly (Model c.h. only)4547411494853 52555450626376158564941416037393940424043445946383384451587764148

Page 74

74Gas assembly6768697071727376777866417775747

Page 75

75Connection pipes79710*80*817710*7980** Not for model c.h. only

Page 76 - Gas assembly

76Control panel and ignition device (Model combi)8553848687899091929394958396977272727272778882

Page 77 - Connection pipes

77Control panel and ignition device (Model c.h. only)85538486878915091929394958396977272727272778882

Page 78

6Figure 4.1: Clearances To Combustible Or Non-combustible MaterialClearance From Hot Water Pipes ToCombustibles = 1”

Page 79

781009910010510610599104981131131137110710710110210310811210877101102103108 901011111109Wiring (Model combi)

Page 80 - Wiring (Model combi)

791009910010510610599104981131131137115210110210315111215177101102103151 901011111109Wiring (Model c.h. only)

Page 81 - Wiring (Model c.h. only)

80Fan, combustion chamber and case panels1291211241251261281211221371231381431141191361351321341221277777777277116771181301441201311391401171421411407

Page 82

81Key no. Description Spare part code1 O-ring gasket 1,78x15,6 BI1001 1312 Drainage valve BI1011 1043 O-ring gasket 17,04x4,00 mm BI1212 1124 Screw M5

Page 83

82Key no. Description Spare part code47 Main exchanger connection clip BI1182 10648 Condensing heat exchanger inlet pipe BI1262 13649 Automatic air pu

Page 84

83Key no. Description Spare part code93 Screw 3,5x16 mm self tap RPH BI1165 10194 Electronic control - ignition p.c.b. BI1555 10795 Fuse 2AF BI1165 11

Page 85

84Key no. Description Spare part code141 Flue thermostat BI1262 104142 Twin fl ue cover plate BI1366 114143 Gasket - Air intake twin kit BI1016 101144

Page 86

852. APPROVED CARBON MONOXIDE DETECTORS.Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 a

Page 87

Manufacturer of Hydronic Heating ProductsP.O. Box 14818 3633 I. StreetPhiladelphia, PA 19134Tel: (215) 535-8900 • Fax: (215) 535-9736 • www.cro

Page 88 - Philadelphia, PA 19134

7V Mounting The BoilerCAUTIONThis boiler weighs approximately 110 pounds:Two people are required to safely lift this boiler onto the wall mounting hoo

Related models: MWC116ELT | MWC Series | MWC116ELL |

Comments to this Manuals

No comments