3) Make sure that the boiler is correctly sized. Use an industry accepted sizing method such as the I=B=R Guide RHH
published by the Air-Conditioning, Heating and Refrigeration Institute (AHRI).
4) In some cases, boilers installed at altitudes above 2000ft may require a different burner conguration from that at sea level.
Consult the local Crown representative for more information.
IV Locating the Boiler
1) Clearances:
Observe the minimum clearances shown below. Except as noted, these clearances apply to all combustible con-
struction, as well as noncombustible walls, ceilings and doors. Also see Figure 2.
Front – 24”
Left Side – 6” (24” for Boilers Equipped with Float Type Low Water Cut-offs)
Right Side – 6” (24” for Boilers Equipped with Tankless Heaters)
Rear – 6” (24” for boilers connected to indirect water heaters)
Top – 6”
Single Wall Chimney Connector (to combustible construction) - 18”
A 24” service clearance from the jacket is recommended from the top of the boiler. This clearance may be
reduced to that shown above; however, servicing the boiler will become increasingly difcult as this clearance
is reduced.
A 24” service clearance is required on the left side of KSZ series boilers equipped with oat type low water cut-
offs. This is to facilitate low water cut-off maintenance.
2) If listed Type L vent is used, follow vent pipe manufacturer recommendations for minimum clearances.
3) Do not install this boiler directly on a combustible surface. Where it is desired to install the KSZ over a non-carpeted com-
bustible surface, install the boiler on the base shown in Figure 3.
4) Do not install this boiler in a location where gasoline or other ammable vapors or liquids will be stored or used. Do not
install this boiler in an area where large amounts of airborne dust will be present, such as a workshop.
WARNING
FAILURE TO OBSERVE THE FOLLOWING LOCATION REQUIREMENTS COULD RESULT
IN PROPERTY DAMAGE, A FIRE, EXPLOSION OR CARBON MONOXIDE (CO) HAZARD.